Net weight |
0.375 kg |
Product or Component Type |
differential thermal overload relay |
Control Type |
blue push-button: reset, red push-button: stop |
[ue] Rated Operational Voltage |
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
Phase Failure Sensitivity |
tripping current 130 % of Ir on two phase, the last one at 0 |
Tripping Threshold |
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Network frequency |
0...400 Hz |
Auxiliary Contact Composition |
1 NO + 1 NC |
Standards |
EN/IEC 60947-4-1,EN/IEC 60947-5-1,UL 60947-4-1,UL 60947-5-1,CSA C22.2 No 60947-4-1,CSA C22.2 No 60947-5-1,GB/T 14048.4,GB/T 14048.5 |
Mechanical Robustness |
shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7,vibrations: 4 gn conforming to IEC 60068-2-6 |
Associated Fuse Rating |
4 A gG for signalling circuit,4 A BS for signalling circuit |
Mounting support |
plate, with specific accessories,rail, with specific accessories,under contactor |
Flame Retardance |
V1 conforming to UL 94 |
Product Compatibility |
LC1D40A,LC1D50A,LC1D65A |
Relay Application |
motor protection |
Thermal Overload Class |
class 20 conforming to IEC 60947-4-1 |
Dielectric Strength |
1.89 kV at 50 Hz conforming to IEC 60947-1 |
Permissible Current |
3 A at 120 V AC-15 for signalling circuit,0.22 A at 125 V DC-13 for signalling circuit |
Device short name |
LRD |
Depth |
123 mm |
Height |
123 mm |
width |
55 mm |
Compatibility code |
LRD |
Network type |
AC,DC |
Range |
TeSys,TeSys Deca |
IP degree of protection |
IP20 conforming to IEC 60529 |
Brand |
Schneider Electric |