TeSys K contactor - 3P - AC-3 <= 440 V 9 A - 1 NO aux. - 110 V AC coil
Incl. Tax
Incl. Tax
All Sellers
Seller | Price | Delivery | Shipping Cost | ||
---|---|---|---|---|---|
View Seller Profile
B2B Network
|
|
Shipping Cost
|
No sellers found for this product.
TeSys K contactor - 3P - AC-3 <= 440 V 9 A - 1 NO aux. - 110 V AC coil
Incl. Tax
Incl. Tax
Description
Product Details
Product or Component Type | contactor |
---|---|
[Uc] Control Circuit Voltage | 110 V AC 50/60 Hz |
auxiliary contacts type | type instantaneous 1 NO |
Pole Contact Composition | 3 NO |
Protective Treatment | TC conforming to IEC 60068,TC conforming to DIN 50016 |
Insulation Resistance | > 10 MOhm for signalling circuit |
Minimum Switching Current | 5 mA for signalling circuit |
Minimum Switching Voltage | 17 V for signalling circuit |
Poles Description | 3P |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
Auxiliary Contact Composition | 1 NO |
Contactor Application | resistive load,motor control |
Non Overlap Distance | 0.5 mm |
Signalling Circuit Frequency | <= 400 Hz |
Range of Product | TeSys K |
Standards | EN/IEC 60947-4-1,GB/T 14048.4,UL 60947-4-1,CSA C22.2 No 60947-4-1,JIS C8201-4-1 |
Mechanical Robustness | shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27,shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27,shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27,shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27,shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27,shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27,vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6,vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
Associated Fuse Rating | 25 A gG at <= 440 V for power circuit,25 A aM for power circuit,10 A gG for signalling circuit conforming to IEC 60947,10 A gG for signalling circuit conforming to VDE 0660 |
Control Circuit Type | AC at 50/60 Hz |
Heat Dissipation | 1.3-1.3 W |
Operating Time | 10...20 ms coil de-energisation and NO opening,10...20 ms coil energisation and NO closing |
Rated Breaking Capacity | 110 A at 415 V conforming to IEC 60947,110 A at 440 V conforming to IEC 60947,80 A at 500 V conforming to IEC 60947,110 A at 220...230 V conforming to IEC 60947,110 A at 380...400 V conforming to IEC 60947,70 A at 660...690 V conforming to IEC 60947 |
Flame Retardance | V1 conforming to UL 94,requirement 2 conforming to NF F 16-101,requirement 2 conforming to NF F 16-102 |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1,B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Device short name | LC1K |
Overvoltage Category | III |
Utilisation category | AC-4,AC-1,AC-3,AC-3e |
Operating altitude | 2000 m without derating |
Compatibility code | LC1K |
Device Application | control |
Range | TeSys |