TeSys GC - modular contactor - 16 A - 2 NO - coil 220...240 V AC
Description
Product Details
Product ID | GC1620M5 |
---|---|
[Ie] Rated Operational Current | 16 A AC-7A |
Operating Position | 30°/vertical |
Product or Component Type | Modular contactor |
[Uc] Control Circuit Voltage | 220...240 V AC 50 Hz |
Control Type | remote control |
Colour | White |
Quantity Per Set | Set of 12 |
Mounting Mode | Clip-on |
Mechanical Durability | 1000000 cycles |
Protective Treatment | TC |
[ue] Rated Operational Voltage | <= 250 V AC |
Poles Description | 2P |
Average Impedance | 2.5 mOhm - Ith 16 A 50 Hz for power circuit |
Contactor Application | Heating Motor control Lighting |
[Uimp] Rated Impulse Wthstand Voltage | 4 kV |
Irms Rated Making Capacity | 40 A at 400 V AC for power circuit conforming to IEC 61095 |
Ambient air temperature for operation | -5…50 °C |
Tightening Torque | Control circuit: 0.8 N.m - on screw clamp terminals
Power circuit: 0.8 N.m - on screw clamp terminals |
Standards |
IEC 61095
IEC 60947-5 |
Mechanical Robustness | Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor open: 2 Gn, 5...300 Hz Vibrations contactor closed: 3 Gn, 5...300 Hz |
[Ith] Conventional Free Air Thermal Current | 16 A (at 50 °C) for power circuit |
[ui] Rated Insulation Voltage | 500 V conforming to IEC 61095
500 V conforming to VDE 0110 |
Associated Fuse Rating | 16 A gL at <= 440 V for power circuit |
Mounting support | DIN rail |
Control Circuit Type | AC at 50 Hz |
Control Circuit Voltage Limits | Drop-out: 0.2...0.75 Uc at 50 Hz (at <50 °C)
Operational: 0.85...1.1 Uc at 50 Hz (at <50 °C) |
Electrical Durability | AC-7A: 100000 cycles
AC-7B: 100000 cycles |
Heat Dissipation | 1.3 W at 50/60 Hz |
Hold-In Power Consumption In VA | 3.8 VA 50 Hz (at 20 °C) |
Inrush Power In VA | 15 VA 50 Hz (at 20 °C) |
Maximum Operating Rate | 300 cyc/h 50 °C |
Operating Time |
10...25 ms opening
10...30 ms closing |
Power Dissipation Per Pole | 0.65 W |
Rated Breaking Capacity | 40 A at 400 V for power circuit conforming to IEC 61095 |
[Icw] rated short-time withstand current | 128 A 40 °C - 10 s for power circuit
40 A 40 °C - 30 s for power circuit |
Device short name | GC16 |
Depth | 62.5 mm |
Ambient air temperature for storage | -40…70 °C |
Height | 81 mm |
width | 17.5 mm |
Utilisation category | AC-7A AC-7B |
Operating altitude | <= 3000 m |
Range | TeSys |
Connections - Terminals | Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 2.5 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1.5 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1.5 mm²solid without cable end Power circuit: screw clamp terminals 1 cable(s) 6 mm²flexible without cable end Power circuit: screw clamp terminals 2 cable(s) 4 mm²flexible without cable end Power circuit: screw clamp terminals 1 cable(s) 6 mm²flexible with cable end Power circuit: screw clamp terminals 2 cable(s) 1.5 mm²flexible with cable end Power circuit: screw clamp terminals 1 cable(s) 6 mm²solid without cable end Power circuit: screw clamp terminals 2 cable(s) 4 mm²solid without cable end |
IP degree of protection | IP40 conforming to VDE 0106 (in enclosure)
IP20 conforming to VDE 0106 |
Product Hover Image | /g/c/gc1620m5.jpg |