TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 220 V DC coil

Product Details

Net weight 0.535 kg
Product or Component Type contactor
[Uc] Control Circuit Voltage 220 V DC
auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1, type mirror contact 1 NC conforming to IEC 60947-4-1
Pole Contact Composition 3 NO
Mechanical Durability 30 Mcycles
Protective Treatment TH conforming to IEC 60068-2-30
Insulation Resistance > 10 MOhm for signalling circuit
Minimum Switching Current 5 mA for signalling circuit
Minimum Switching Voltage 17 V for signalling circuit
Poles Description 3P
Average Impedance 2 mOhm - Ith 50 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
Contact Compatibility M4
Contactor Application resistive load,motor control
Protective Cover with
Signalling Circuit Frequency 25...400 Hz
Time Constant 28 ms
Range of Product TeSys Deca
Standards IEC 60335-1
Mechanical Robustness vibrations contactor open (2 Gn, 5...300 Hz),vibrations contactor closed (4 Gn, 5...300 Hz),shocks contactor closed (15 Gn for 11 ms),shocks contactor open (8 Gn for 11 ms)
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1,63 A gG at <= 690 V coordination type 1 for power circuit,63 A gG at <= 690 V coordination type 2 for power circuit
Mounting support rail,plate
Control Circuit Type DC standard
Electrical Durability 1.65 Mcycles 32 A AC-3 at Ue <= 440 V,1.4 Mcycles 50 A AC-1 at Ue <= 440 V,1.65 Mcycles 32 A AC-3e at Ue <= 440 V
Operating Time 53.55...72.45 ms closing,16...24 ms opening
Power Dissipation Per Pole 2 W AC-3,5 W AC-1,2 W AC-3e
Rated Breaking Capacity 550 A at 440 V for power circuit conforming to IEC 60947
Flame Retardance V1 conforming to UL 94
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1,B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Coil Technology built-in bidirectional peak limiting diode suppressor
Motor Power Hp 2 hp at 115 V AC 50/60 Hz for 1 phase motors,5 hp at 230/240 V AC 50/60 Hz for 1 phase motors,7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors,10 hp at 230/240 V AC 50/60 Hz for 3 phases motors,20 hp at 460/480 V AC 50/60 Hz for 3 phases motors,30 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Device short name LC1D
Depth 101 mm
Height 85 mm
Overvoltage Category III
width 45 mm
Pollution degree 3
Utilisation category AC-4,AC-3,AC-1,AC-3e
Operating altitude 0...3000 m
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact,1.5 ms on energisation between NC and NO contact
Compatibility code LC1D
IP degree of protection IP20 front face conforming to IEC 60529