Product Details
Net weight | 0.13 kg |
---|---|
Product or Component Type | differential thermal overload relay |
Control Type | push-button green reset:, push-button red stop: |
Colour | grey (RAL 7011) |
Protective Treatment | TH conforming to IEC 60068 |
[ue] Rated Operational Voltage | <= 690 V AC |
Phase Failure Sensitivity | tripping current 130 % of Ir on two phase, the last one at 0 conforming to IEC 60947-4-1 |
Tripping Threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
Network frequency | 50...60 Hz |
Auxiliary Contact Composition | 1 NO + 1 NC |
Standards | IEC 60947-4-1,IEC 60947-5-1 |
Mechanical Robustness | shocks: 6 Gn for 11 ms conforming to IEC 60068-2-7,vibrations: 3 GN conforming to IEC 60068-2-6 |
Associated Fuse Rating | 2 A gG for power circuit,0.25 A aM for power circuit,5 A gG for signalling circuit |
Mounting support | under contactor,plate, with specific accessories,rail, with specific accessories |
Range | EasyPact |
Depth | 70 mm |
Device short name | LRE |
Electromagnetic Compatibility | surge withstand: 6 kV conforming to IEC 60801-5 |
Height | 44.5 mm |
IP degree of protection | IP20 conforming to IEC 60529 |
Dielectric Strength | 6 kV at 50 Hz conforming to IEC 60255-5 |
Local Signalling | trip indicator |
width | 45 mm |
Product Compatibility | LC1E06...38 |
Signalling Function | relay trip indicator |
Network type | AC |
Relay Application | motor protection |
Thermal Overload Class | class 10A conforming to IEC 60947-4-1 |
Brand | Schneider Electric |