residual current protection relay, Vigirex RH10M, 30 mA, 220/240 VAC 50/60 Hz, DIN rail mounting

56130
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Description

Product Details

Activity PPCCB
[uimp] Rated Impulse Withstand Voltage 8 kV
[us] Rated Supply Voltage 220...240 V AC 50/60 Hz 55...110 % , 220...240 V AC 50/60 Hz 55...110 % , 220...240 V AC 50/60 Hz 55...110 % , 220...240 V AC 50/60 Hz 55...110 %
Ambient Air Temperature for Operation -35-70 °C
Ambient Air Temperature for Storage -55-85 °C
Compatibility Code RH10M
Depth 74 mm
Device Short Name RH10M
Electromagnetic Compatibility conducted and radiated emissions: , B, conforming to CISPR 11
Height 8.0 cm
Ik Degree of Protection IK07 conforming to EN 50102
Ip Degree of Protection IP40 on front face: conforming to EN/IEC 60529
Mechanical Robustness fire resistance conforming to IEC 60695-2-1
Minimum Load 10 mA at 12 V , 10 mA at 12 V
Mounting Support DIN rail
Net Weight 0.3 kg
Overvoltage Category IV
Product or Component Type residual current protection relay
Range VigiPacT
Range Compatibility TOA earth leakage current sensor
Tightening Torque auxiliary power supply: 0.6-0.6 N.m top
Width 8.6 cm
Wire Stripping Length auxiliary power supply: 7 mm for top connection
9 Mm Pitches 6
Connections - Terminals auxiliary power supply: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12
[ithe] Conventional Enclosed Thermal Current 8 A
Earth Leakage Current 0.03-0.03 A
Earthing System TN-S|IT|TT
Electrical Shock Protection Class class II
Monitoring electronics (continuous)
Network Rated Voltage 1000-1000 V - AC at 50/60 Hz (maximum)
Power Consumption in Va 4 VA
Relay Application protection relay
Reset manual reset
Residual Earth-leakage Sensitity Adjustment Type fixed
Residual Earth-leakage Time Delay Adjustment Type instantaneous
Tamperproof of Settings protected by sealable cover
Test Function local
Type of Measurement earth fault current internal measurement, range: 80...100 %
Type of Setting none
Earth-leakage protection class type A
Earth-leakage Protection Class type A
Pollution Degree 3 conforming to IEC 60664-1
Relative Humidity 95-95 % at 55-55 °C
Range VigiPacT
Range Compatibility VigiPacT TOA earth leakage current sensor , VigiPacT TOA earth leakage current sensor , VigiPacT TOA earth leakage current sensor , VigiPacT A earth leakage current sensor , VigiPacT A earth leakage current sensor , VigiPacT A earth leakage current sensor , VigiPacT L earth leakage current sensor , VigiPacT L earth leakage current sensor , VigiPacT L earth leakage current sensor
Network Rated Voltage 1000-1000 V - AC at 50/60 Hz (maximum) , 1000-1000 V - AC at 50/60 Hz (maximum) , 1000-1000 V - AC at 50/60 Hz (maximum) , 1000-1000 V - AC at 50/60 Hz (maximum) , 1000-1000 V - AC at 400 Hz (maximum) , 1000-1000 V - AC at 400 Hz (maximum) , 1000-1000 V - AC at 400 Hz (maximum) , 1000-1000 V - AC at 400 Hz (maximum)
Residual Earth-leakage Time Delay Adjustment Type instantaneous
Length 9.0 cm

Seller Information

Documents

Extended Warranty

Reviews

Write Your Own Review
You're reviewing: residual current protection relay, Vigirex RH10M, 30 mA, 220/240 VAC 50/60 Hz, DIN rail mounting
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.