Activity |
IDVSD |
Part Number |
ATS01N209QN |
[Uc] control circuit voltage |
built into the starter |
[Us] rated supply voltage |
380...415 V - 10...10 % |
ambient air temperature for storage |
-25-70 °C conforming to EN/IEC 60947-4-2 |
compatibility code |
ATS01N2 |
current consumption |
45 A at nominal load |
depth |
131 mm |
device short name |
ATS01 |
operating altitude |
<= 1000 m without derating, > 1000 m with current derating of 2.2 % per additional 100 m |
operating position |
vertical +/- 10 degree |
output voltage |
<= power supply voltage |
pollution degree |
2 conforming to EN/IEC 60947-4-2 |
power dissipation in W |
4 W at full load and at end of starting, 94 W in transient state |
power range |
4-6 kW at 380-440 V 3 phases |
product certifications |
GOST, B44.1-96/ASME A17.5 for starter wired to the motor delta terminal, CCC, CSA, C-Tick, UL |
product or component type |
soft starter |
range of product |
Altistart 01 |
relative humidity |
5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
shock resistance |
15 gn for 11 ms conforming to EN/IEC 60068-2-27 |
supply voltage limits |
342-456 V |
tightening torque |
0.5-0.5 N.m, 1.9-2.5 N.m |
utilisation category |
AC-53B conforming to EN/IEC 60947-4-2 |
width |
45 mm |
IcL starter rating |
9:00 AM |
Discrete output current |
2 A DC-13, 3 A AC-15 |
Type of start |
start with voltage ramp |
Starting time |
1 s / 100 , 5 s / 20 , 10 s / 10 , adjustable from 1 to 10 s |
Assembly style |
with heat sink |
Starting torque |
30...80 % of starting torque of motor connected directly on the line supply |
Supply frequency |
50...60 Hz - 5...5 % |
Discrete input voltage |
24...40 V |
Discrete input type |
logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm |
Discrete output type |
open collector logic LO1 end of starting signal, relay outputs R1A, R1C NO |
Maximum switching current |
relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load, relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load |
Discrete input logic |
positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA |
Discrete output voltage |
24 V (voltage limits: 6...30 V) open collector logic |
Deceleration time symb |
adjustable from 1 to 10 s |
vibration resistance |
1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6, 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6 |
ambient air temperature for operation |
-10-40 °C (without derating), 40-50 °C (with current derating of 2 % per °C) |
standards |
EN/IEC 60947-4-2 |
Display Type |
1 LED (green) for starter powered up, 1 LED (yellow) for nominal voltage reached |