Motor circuit breaker,TeSys Deca,3P,25A,magnetic,rotary handle,screw clamp terminals

Product Details

Activity PPCTR
Weight (in Kg) 2.4 kg
[ith] Conventional Free Air Thermal Current 25 A conforming to IEC 60947-4-1
Product Name TeSys GV2, TeSys Deca
[ue] Rated Operational Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Product or Component Type motor circuit breaker
Range TeSys Deca
Device Application motor protection
Direct Connector without
Control Type rotary handle
Fire Resistance 960 °C conforming to IEC 60695-2-11
Magnetic Tripping Current 327-327 A
Maximum Operating Rate 40 cyc/h
Poles Description 3P
Rated Duty continuous conforming to IEC 60947-4-1
Operating Altitude 2000 m
Network Frequency 50/60 Hz conforming to IEC 60947-2
Net Weight 0.33 kg
Suitability for Isolation yes conforming to IEC 60947-1 § 7-1-6
Trip Unit Technology magnetic
Mechanical Durability 100000 cycles
[ics] Rated Service Short-Circuit Breaking Capacity 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2, 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Standards CSA C22.2 No 60947-4-1#|#UL 60947-4-1#|#EN/IEC 60947-2
Power Dissipation per Pole 1.8 W
Utilisation Category category A conforming to IEC 60947-2, AC-3 conforming to IEC 60947-4-1
Ambient Air Temperature for Operation -20-60 °C
[uimp] Rated Impulse withstand Voltage 6 kV conforming to IEC 60947-2
Ambient Air Temperature for Storage -40-80 °C
Compatibility Code GV2L
Breaking Capacity 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2, 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
Product Certifications IECEE CB Scheme#|#UL#|#CSA#|#CCC#|#EAC#|#RINA#|#LROS (Lloyds register of shipping)#|#DNV-GL#|#BV#|#UKCA
[in] Rated Current 25 A
Height 89 mm
Depth 97 mm
Width 45 mm