TeSys Deca contactor,4P(2NO+2NC),AC-1,=440V 40A,48V AC coil

LC1D258E7
Be the first one to review this.

Excl. Tax

login_green To View the best prices please Sign in / Register.
loader
Loading...

Description

TeSys Deca contactor,4P(2NO+2NC),AC-1,=440V 40A,48V AC coil

Product Details

Activity PPCTR
Weight (in Kg) 0.414 kg
[ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit, 40 A (at 60 °C) for power circuit
Pole Contact Composition 2 NO + 2 NC
[ue] Rated Operational Voltage power circuit: <= 690 V AC 25...400 Hz
Product or Component Type contactor
[uc] Control Circuit Voltage 48 V AC 50/60 Hz
Control Circuit Type AC at 50/60 Hz
Control Circuit Voltage Limits 0.3...0.6 Uc (-40-60 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz, 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
Fire Resistance 850 °C conforming to IEC 60695-2-1
Maximum Operating Rate 3600 cyc/h 60 °C
Operating Time 12...22 ms closing, 4...19 ms opening
Poles Description 4P
Operating Altitude 0...3000 m
Net Weight 0.425 kg
Mechanical Durability 15 Mcycles
Standards EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4
Power Dissipation per Pole 3.2 W AC-1
Utilisation Category AC-1
[icw] Rated Short-Time withstand Current 240 A 40 °C - 10 s for power circuit, 380 A 40 °C - 1 s for power circuit, 50 A 40 °C - 10 min for power circuit, 120 A 40 °C - 1 min for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit
[uimp] Rated Impulse withstand Voltage 6 kV conforming to IEC 60947
[ie] Rated Operational Current 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Compatibility Code LC1D
Product Certifications UL#|#CSA#|#CCC#|#EAC#|#UKCA#|#CB#|#EU-RO-MR by DNV-GL
[ui] Rated Insulation Voltage power circuit: 690 V conforming to IEC 60947-4-1, power circuit: 600 V CSA certified, power circuit: 600 V UL certified, signalling circuit: 690 V conforming to IEC 60947-1, signalling circuit: 600 V CSA certified, signalling circuit: 600 V UL certified
Height 105 mm
Depth 99 mm
Width 45 mm
Range TeSys

Seller Information

Documents

Extended Warranty

Reviews

Write Your Own Review