OVERVOLTAGE CONTROL RELAY RM22-UA - RANG

RM22UA33MR
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Description

Modular 1 phaseVoltage control relay, Harmony, 8A, 2CO, 15…500V AC DC, 24…240V AC DC

Product Details

Activity IDSIG
Dielectric Test Voltage 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Functionality undervoltage and overvoltage in window mode
Hysteresis 3-3 % fixed of full scale for window mode, 5-50 % adjustable of threshold setting
Immunity to Microbreaks 10 ms
Maximum Measuring Cycle 100 ms measurement cycle as true rms value
Maximum Switching Voltage 250 V AC
Shock Resistance 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27, 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
Measurement Error < 1 % over the whole range with voltage variation, 0.05 %/°C with temperature variation
Measurement Range 15...500 V voltage AC/DC 50/60 Hz
Mounting Support 35 mm DIN rail conforming to EN/IEC 60715
Nominal Output Current 8 A
Mechanical Durability 10000000 cycles
Overvoltage Category III conforming to IEC 60664-1
Pollution Degree 3 conforming to IEC 60664-1
Power Consumption in VA 3.5-3.5 VA AC
Net Weight 0.11 kg
Relative Humidity 93-97 % at 25-55 °C conforming to IEC 60068-2-30
Relay Monitored Parameters undervoltage and overvoltage in window mode#|#overvoltage or undervoltage detection
Relay Name RM22UA
Relay Type voltage control relay
Repeat Accuracy +/- 0.5 % for input and measurement circuit, +/- 2 % for time delay
Reset Time 1500 ms at maximum voltage
Safety Reliability Data MTTFd = 308.2 years#|#B10d = 290000
Tightening Torque 0.6-1 N.m conforming to IEC 60947-1
Vibration Resistance 0.075 mm (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6, 1 gn (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6, 0.035 mm (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6, 0.5 gn (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6
Weight (in Kg) 0.45 kg
Ambient Air Temperature for Storage -40-70 °C
Maximum Switching Current 8 A AC
[us] Rated Supply Voltage 24...240 V AC/DC 50/60 Hz
Compatibility Code RM22
Connections - Terminals screw connectors
Insulation Resistance > 100 MOhm at 500 V DC
[in] Rated Current 8 A
[uc] Control Circuit Voltage 24...240 V
Housing Material self-extinguishing plastic
Minimum Switching Current 10 mA at 5 V DC
Ambient Air Temperature for Operation -20-50 °C at 60 Hz, -20-60 °C at 50 Hz
Range of Product Harmony Control Relays
Product or Component Type voltage control relay
Width 22.5 mm

Seller Information

Documents

Reviews

Write Your Own Review
You're reviewing: OVERVOLTAGE CONTROL RELAY RM22-UA - RANG
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.