[us] Rated Supply Voltage |
380...460 V - 15...10 % |
Ambient Air Temperature for Operation |
-15-45 °C (without derating), 45-60 °C (with derating factor) |
Ambient Air Temperature for Storage |
-40-70 °C |
Weight (in Kg) |
1kg |
Motor Power kW |
18.5 kW for normal duty, 15 kW for heavy duty |
Power Dissipation in W |
410 W(forced convection) at 380 V, 64 W(natural convection) at 380 V, switching frequency 4 kHz |
Device Short Name |
ATV610 |
Product or Component Type |
variable speed drive |
Product Specific Application |
fan, pump, compressor, conveyor |
Range of Product |
Easy Altivar 610 |
Communication Port Protocol |
Modbus serial |
Connector Type |
1 RJ45 (on the remote graphic terminal) for Modbus serial |
Discrete Input Number |
6 |
Discrete Input Type |
DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm, DI5, DI6 programmable as pulse input: 0-30 kHz, 24 V DC (<= 30 V) |
Height |
495 mm, 580 mm with EMC plate |
Electromagnetic Compatibility |
electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2, radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3, electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5, conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Marking |
CE |
Minimum Switching Current |
relay output R1, R2, R3: 5 mA at 24 V DC |
Network Number of Phases |
3 phases |
Net Weight |
13.5 kg |
Noise Level |
65 dB conforming to 86/188/EEC |
Operating Position |
vertical +/- 10 degree |
Operating Altitude |
<= 1000 m without derating, 1000...4800 m with current derating 1 % per 100 m |
Supply Frequency |
50...60 Hz +/-5 % |
Transmission Rate |
4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
Maximum Switching Current |
relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 250 V AC, relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 30 V DC, relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC, relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
Protection Type |
thermal protection: motor, motor phase break: motor, thermal protection: drive, overheating: drive, overcurrent between output phases and earth: drive, overload of output voltage: drive, short-circuit protection: drive, motor phase break: drive, overvoltages on the DC bus: drive, line supply overvoltage: drive, line supply undervoltage: drive, line supply phase loss: drive, overspeed: drive, break on the control circuit: drive |
Depth |
232 mm |
Width |
211 mm |
Standards |
EN/IEC 61800-3, environment 2 category C3 EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 60721-3 |
Discrete Input Logic |
positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1), negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1), positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1) |