Description

Acti9 iC60H 1P 6A C Miniature Circuit breaker

Product details

  • Activity
    HDCFD
  • [in] Rated Current
    6:00 AM
  • [ui] Rated Insulation Voltage
    500 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • [uimp] Rated Impulse withstand Voltage
    6 kV conforming to EN/IEC 60947-2
  • Ambient Air Temperature for Operation
    -35-70 °C
  • [ue] Rated Operational Voltage
    240 V AC 50/60 Hz
  • Ambient Air Temperature for Storage
    -40-85 °C
  • Breaking Capacity Code
    H
  • Compatibility Code
    iC60
  • Control Type
    toggle
  • Curve Code
    C
  • Breaking Capacity
    20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2, 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2, 10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1, 42 kA Icu at 10...60 V AC 50/60 Hz conforming to EN/IEC 60947-2, 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2, 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • Depth
    78.5 mm
  • Device Short Name
    iC60H
  • IP Degree of Protection
    IP20 conforming to IEC 60529
  • Net Weight
    0.125 kg
  • Mechanical Durability
    20000 cycles
  • Mounting Mode
    clip-on
  • Network Frequency
    50/60 Hz
  • Poles Description
    1P
  • Network Type
    AC
  • Product or Component Type
    miniature circuit-breaker
  • 9 mm Pitches
    2
  • Number of Protected Poles
    1
  • Product Name
    Disbo iC60
  • Provision for Padlocking
    padlockable
  • Range
    Acti9
  • Relative Humidity
    95-95 % at 55-55 °C
  • Mounting Support
    rail
  • Standards
    EN/IEC 60898-1#|#EN/IEC 60947-2
  • Tightening Torque
    2-2 N.m top or bottom
  • Trip Unit Technology
    thermal-magnetic
  • Wire Stripping Length
    14 mm for top or bottom connection
  • Colour
    white
  • Tropicalisation
    2 conforming to IEC 60068-1
  • [lcs] Rated Service Breaking Capacity
    10 kA 100 % conforming to EN/IEC 60947-2 - 72 V DC, 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz, 20 kA 100 % conforming to EN/IEC 60947-2 - 12...48 V DC, 21 kA 50 % conforming to EN/IEC 60947-2 - 10...60 V AC 50/60 Hz, 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz, 7500 A 75 % conforming to EN/IEC 60898-1 - 240 V AC 50/60 Hz
  • Connections - Terminals
    single terminal (top or bottom) 1-25 mm² rigid, single terminal (top or bottom) 1-16 mm² flexible