3P Cont 95A AC3 440V 45kW – 110V AC Coil

LC1D95F7
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Description

contactor, TeSys Deca, 3P(3NO), AC-3/AC-3e, 440V, 95A, 110V AC 50/60Hz coil

Product Details

Activity PPCTR
Weight (in Kg) 0.86 kg
[ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit, 125 A (at 60 °C) for power circuit
Pole Contact Composition 3 NO
Range of Product TeSys D
[ue] Rated Operational Voltage power circuit: 1000 V AC 25...400 Hz
Product or Component Type contactor
[uc] Control Circuit Voltage 110 V AC 50/60 Hz
Range TeSys
Control Circuit Type AC at 50/60 Hz standard
Control Circuit Voltage Limits 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz, 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz, 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz
Fire Resistance 850 °C conforming to IEC 60695-2-1
Maximum Operating Rate 3600 cyc/h 60 °C
Operating Time 20...35 ms closing, 6...20 ms opening
Poles Description 3P
Operating Altitude 0...3000 m
Net Weight 1.61 kg
Mechanical Durability 4 Mcycles
Standards EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No 60947-4-1, CSA C22.2 No 60947-5-1, GB/T 14048.4
Power Dissipation per Pole 12.5 W AC-1, 7.2 W AC-3, 7.2 W AC-3e
Utilisation Category AC-1#|#AC-4#|#AC-3#|#AC-3e
[icw] Rated Short-Time withstand Current 1100 A 40 °C - 1 s for power circuit, 800 A 40 °C - 10 s for power circuit, 400 A 40 °C - 1 min for power circuit, 135 A 40 °C - 10 min for power circuit, 140 A - 100 ms for signalling circuit, 120 A - 500 ms for signalling circuit, 100 A - 1 s for signalling circuit
[uimp] Rated Impulse withstand Voltage 8 kV conforming to IEC 60947
[ie] Rated Operational Current 95 A (at <60 °C) at <= 440 V AC-3 for power circuit, 125 A (at <60 °C) at <= 690 V AC-1 for power circuit, 95 A (at <60 °C) at <= 440 V AC-3e for power circuit
Compatibility Code LC1D
Product Certifications IECEE CB Scheme#|#UL#|#CSA#|#CCC#|#EAC#|#LROS (Lloyds register of shipping)#|#RINA#|#BV#|#DNV-GL
[ui] Rated Insulation Voltage power circuit: 1000 V conforming to IEC 60947-4-1, power circuit: 600 V CSA certified, power circuit: 600 V UL certified, signalling circuit: 690 V conforming to IEC 60947-1, signalling circuit: 600 V CSA certified, signalling circuit: 600 V UL certified
Height 127 mm
Depth 130 mm
Width 85 mm

Seller Information

Documents

Reviews

Write Your Own Review
You're reviewing: 3P Cont 95A AC3 440V 45kW – 110V AC Coil
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.