Schneider Electric TeSys K contactor - 3P - AC-3 <= 440 V 9 A - 1 NO aux. - 220...230 V AC coil
Incl. Tax
Incl. Tax
All Sellers
Seller | Price | Delivery | Shipping Cost | ||
---|---|---|---|---|---|
View Seller Profile
B2B Network
|
|
Shipping Cost
|
No sellers found for this product.
Schneider Electric TeSys K contactor - 3P - AC-3 <= 440 V 9 A - 1 NO aux. - 220...230 V AC coil
Incl. Tax
Incl. Tax
Description
TeSys K contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3 (4kW@400V), and for non-inductive load control applications up to 20A/690V AC-1. It provides a 220V 50/60Hz AC coil, 1NO built-in auxiliary contact, connection by screw clamp terminals. For operating rates until 600 cycles/hour and environments until 50°C, it procures reliability and durability to standard applications. Very compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Product Details
Weight (in Kg) | 0.1782 |
---|---|
auxiliary contacts type | type instantaneous 1 NO |
Pole Contact Composition | 3 NO |
Product Or Component Type | contactor |
Protective Treatment | TC conforming to IEC 60068 TC conforming to DIN 50016 |
Insulation Resistance | > 10 MOhm for signalling circuit |
Minimum Switching Current | 5 mA for signalling circuit |
Minimum Switching Voltage | 17 V for signalling circuit |
Poles Description | 3P |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
Auxiliary Contact Composition | 1 NO |
Contactor Application | motor control resistive load |
Non Overlap Distance | 0.5 mm |
Signalling Circuit Frequency | <= 400 Hz |
Irms Rated Making Capacity | 110 A AC for power circuit conforming to NF C 63-110 110 A AC for power circuit conforming to IEC 60947 110 A AC for signalling circuit conforming to IEC 60947 |
Range of Product | TeSys K |
Product Certifications | CSA UL UKCA |
Mechanical Robustness | shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
[Ith] Conventional Free Air Thermal Current | 20 A (at 50 °C) for power circuit 10 A (at 50 °C) for signalling circuit |
Associated Fuse Rating | 25 A gG at <= 440 V for power circuit 25 A aM for power circuit 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660 |
Control Circuit Type | AC at 50/60 Hz |
Control Circuit Voltage Limits | operational: 0.8...1.15 Uc (at <50 °C) drop-out: 0.2...0.75 Uc (at <50 °C) |
Heat Dissipation | 1.3-1.3 W |
Hold-In Power Consumption In VA | 4.5-4.5 VA (at 20 °C) |
Inrush Power In VA | 30-30 VA (at 20 °C) |
Maximum Operating Rate | 3600 cyc/h |
Motor Power Kw | 2.2 kW at 220...230 V AC 50/60 Hz AC-3 4 kW at 380...415 V AC 50/60 Hz AC-3 4 kW at 440 V AC 50/60 Hz AC-3 4 kW at 480 V AC 50/60 Hz AC-3 4 kW at 500...600 V AC 50/60 Hz AC-3 4 kW at 660...690 V AC 50/60 Hz AC-3 2.2 kW at 400 V AC 50/60 Hz AC-4 |
Operating Time | 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing |
Rated Breaking Capacity | 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947 |
Flame Retardance | V1 conforming to UL 94 requirement 2 conforming to NF F 16-101 requirement 2 conforming to NF F 16-102 |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Overvoltage Category | III |
Utilisation category | AC-4 AC-3 AC-1 |
Operating altitude | 2000 m without derating |
Compatibility code | LC1K |
Device Application | control |
[Uc] Control Circuit Voltage | 220...230 V AC 50/60 Hz |
Brand | Schneider Electric |