Schneider Electric TeSys D control relay - 5 NO - <= 690 V - 24 V DC standard coil

CAD50BD
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Description

TeSys D control relay, 5 contacts (5NO), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 24V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).

Product Details

Activity PPCTR
Weight (in Kg) 0.527
Net weight 0.58 kg
Pole Contact Composition 5 NO
Product Or Component Type control relay
Mechanical Durability 30 Mcycles
Protective Treatment TH conforming to IEC 60068
Insulation Resistance > 10 MOhm
Minimum Switching Current 5 mA
Minimum Switching Voltage 17 V
Contactor Application control circuit
Hold-in Power Consumption In W 5.4-5.4 W at 20 °C
Time Constant 28 ms
[IP] Degree of Protection IP2x front face conforming to VDE 0106
Connections Terminals screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
[Uimp] Rated Impulse Wthstand Voltage 6 kV conforming to IEC 60947
Irms Rated Making Capacity 140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
Ambient air temperature for operation -40-60 °C
60-70 °C with derating
Range of Product TeSys D control relay
Tightening Torque 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Standards BS 4794
EN 60947-5
IEC 60947-5-1
NF C 63-140
VDE 0660
IEC 60335-1
Product Certifications CSA
UL
UKCA
Mechanical Robustness shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C)
[ui] Rated Insulation Voltage 600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1
Associated Fuse Rating 10 A gG conforming to IEC 60947-5-1
Mounting support rail
plate
Control Circuit Type DC standard
Control Circuit Voltage Limits 0.1...0.25 Uc (-40-70 °C):drop-out DC
0.7...1.25 Uc (-40-60 °C):operational DC
1...1.25 Uc (60-70 °C):operational DC
Maximum Operating Rate 180 cyc/mn
Operating Time 53...72 ms coil energisation and NO closing
16...24 ms coil de-energisation and NO opening
[Icw] rated short-time withstand current 100 A - 1 s
120 A - 500 ms
140 A - 100 ms
Inrush Power In W 5.4-5.4 W (at 20 °C)
Device short name CAD
Depth 93 mm
Ambient air temperature for storage -60-80 °C
Height 77 mm
width 45 mm
Utilisation category AC-14
DC-13
AC-15
Operating altitude 0...3000 m
Non-Overlap Time 1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Compatibility code CAD
[Uc] Control Circuit Voltage 24 V DC
[Ue] Rated Operational Voltage <= 690 V AC 25...400 Hz
Brand Schneider Electric

Seller Information

Documents

Reviews

Write Your Own Review
You're reviewing: Schneider Electric TeSys D control relay - 5 NO - <= 690 V - 24 V DC standard coil
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.