Schneider Electric TeSys D control relay - 3 NO + 2 NC - <= 690 V - 24 V DC standard coil
Incl. Tax
Incl. Tax
All Sellers
Seller | Price | Delivery | Shipping Cost | ||
---|---|---|---|---|---|
View Seller Profile
B2B Network
|
|
Shipping Cost
|
No sellers found for this product.
Schneider Electric TeSys D control relay - 3 NO + 2 NC - <= 690 V - 24 V DC standard coil
Incl. Tax
Incl. Tax
Description
TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 24V DC control circuit with no inrush consumption and equipped with a surge suppression device, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).
Product Details
Weight (in Kg) | 0.528 |
---|---|
Net weight | 0.58 kg |
Pole Contact Composition | 3 NO + 2 NC |
Product Or Component Type | control relay |
Mechanical Durability | 30 Mcycles |
Protective Treatment | TH conforming to IEC 60068 |
Insulation Resistance | > 10 MOhm |
Minimum Switching Current | 5 mA |
Minimum Switching Voltage | 17 V |
Contactor Application | control circuit |
Hold-in Power Consumption In W | 5.4-5.4 W at 20 °C |
Time Constant | 28 ms |
[IP] Degree of Protection | IP2x front face conforming to VDE 0106 |
Connections Terminals | screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end |
[Uimp] Rated Impulse Wthstand Voltage | 6 kV conforming to IEC 60947 |
Irms Rated Making Capacity | 140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 |
Ambient air temperature for operation | -40-60 °C 60-70 °C with derating |
Range of Product | TeSys D control relay |
Tightening Torque | 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Standards | BS 4794 EN 60947-5 IEC 60947-5-1 NF C 63-140 VDE 0660 IEC 60335-1 |
Product Certifications | UL CSA UKCA |
Mechanical Robustness | shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
[Ith] Conventional Free Air Thermal Current | 10 A (at 60 °C) |
[ui] Rated Insulation Voltage | 600 V UL certified 600 V CSA certified 690 V conforming to IEC 60947-5-1 |
Associated Fuse Rating | 10 A gG conforming to IEC 60947-5-1 |
Mounting support | rail plate |
Control Circuit Type | DC standard |
Control Circuit Voltage Limits | 0.1...0.25 Uc (-40-70 °C):drop-out DC 0.7...1.25 Uc (-40-60 °C):operational DC 1...1.25 Uc (60-70 °C):operational DC |
Maximum Operating Rate | 180 cyc/mn |
Operating Time | 53...72 ms coil energisation and NO closing 16...24 ms coil de-energisation and NO opening 47...63 ms coil energisation and NC opening 15...25 ms coil de-energisation and NC closing |
[Icw] rated short-time withstand current | 100 A - 1 s 120 A - 500 ms 140 A - 100 ms |
Inrush Power In W | 5.4-5.4 W (at 20 °C) |
Device short name | CAD |
Depth | 93 mm |
Ambient air temperature for storage | -60-80 °C |
Height | 77 mm |
width | 45 mm |
Utilisation category | DC-13 AC-15 AC-14 |
Operating altitude | 0...3000 m |
Non-Overlap Time | 1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact |
Compatibility code | CAD |
[Uc] Control Circuit Voltage | 24 V DC |
[Ue] Rated Operational Voltage | <= 690 V AC 25...400 Hz |
Brand | Schneider Electric |