Schneider Electric TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 125 A - 220 V AC 50/60 Hz coil
Incl. Tax
Incl. Tax
All Sellers
Seller | Price | Delivery | Shipping Cost | ||
---|---|---|---|---|---|
View Seller Profile
B2B Network
|
|
Shipping Cost
|
No sellers found for this product.
Schneider Electric TeSys D contactor - 4P(4 NO) - AC-1 - <= 440 V 125 A - 220 V AC 50/60 Hz coil
Incl. Tax
Incl. Tax
Description
TeSys Deca contactor, 4-pole (4NO), for non-inductive load applications up to 125A/1000V AC-1. It provides a 220V 50/60Hz AC coil, power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (96mm width), DIN-rail mounting or screw fixing. Without build-in auxiliary contacts, side and front mounting auxiliary contact blocks available (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Product Details
Weight (in Kg) | 1.701 |
---|---|
Net weight | 1.76 kg |
Pole Contact Composition | 4 NO |
Product Or Component Type | contactor |
Mechanical Durability | 4 Mcycles |
Protective Treatment | TH conforming to IEC 60068-2-30 |
Poles Description | 4P |
Average Impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
Contact Compatibility | M1 |
Contactor Application | resistive load |
Protective Cover | without |
[IP] Degree of Protection | IP20 front face conforming to IEC 60529 |
Connections Terminals | control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end power circuit: connector 1 cable(s) 4-50 mm²solid without cable end power circuit: connector 2 cable(s) 4-25 mm²solid without cable end |
[Uimp] Rated Impulse Wthstand Voltage | 8 kV conforming to IEC 60947 |
Irms Rated Making Capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
Ambient air temperature for operation | -40-60 °C 60-70 °C with derating |
Range of Product | TeSys D |
Tightening Torque | control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm power circuit: 12 N.m - on connector hexagonal screw head 4 mm control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
Product Certifications | DNV LROS (Lloyds register of shipping) GL CSA CCC RINA UL GOST BV |
Mechanical Robustness | vibrations contactor open: 2 Gn, 5...300 Hz shocks contactor open: 8 Gn for 11 ms vibrations contactor closed: 3 Gn, 5...300 Hz shocks contactor closed: 10 Gn for 11 ms |
[Ith] Conventional Free Air Thermal Current | 125 A (at 60 °C) for power circuit |
[ui] Rated Insulation Voltage | power circuit: 600 V CSA certified power circuit: 600 V UL certified power circuit: 1000 V conforming to IEC 60947-4-1 |
Associated Fuse Rating | 200 A gG at <= 690 V coordination type 1 for power circuit 160 A gG at <= 690 V coordination type 2 for power circuit |
Mounting support | rail plate |
Control Circuit Type | AC at 50/60 Hz |
Control Circuit Voltage Limits | 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz 1...1.1 Uc (55-70 °C):operational AC 50/60 Hz |
Electrical Durability | 0.8 Mcycles 125 A AC-1 at Ue <= 440 V |
Fire Resistance | 850 °C conforming to IEC 60695-2-1 |
Heat Dissipation | 6-10 W at 50/60 Hz |
Hold-In Power Consumption In VA | 26-26 VA 60 Hz cos phi 0.3 (at 20 °C) 26-26 VA 50 Hz cos phi 0.3 (at 20 °C) |
Inrush Power In VA | 245-245 VA 60 Hz cos phi 0.75 (at 20 °C) 245-245 VA 50 Hz cos phi 0.75 (at 20 °C) |
Maximum Operating Rate | 3600 cyc/h 60 °C |
Operating Time | 20...35 ms closing 6...20 ms opening |
Power Dissipation Per Pole | 12.5 W AC-1 |
Rated Breaking Capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 640 A 40 °C - 10 s for power circuit 990 A 40 °C - 1 s for power circuit 135 A 40 °C - 10 min for power circuit 320 A 40 °C - 1 min for power circuit |
Flame Retardance | V1 conforming to UL 94 |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Climatic Withstand | conforming to IACS E10 |
Coil Technology | without built-in suppressor module |
Device short name | LC1D |
Depth | 125 mm |
Ambient air temperature for storage | -60-80 °C |
Height | 127 mm |
Overvoltage Category | III |
width | 96 mm |
Pollution degree | 3 |
Utilisation category | AC-1 |
Operating altitude | 0...3000 m |
Compatibility code | LC1D |
[Uc] Control Circuit Voltage | 220 V AC 50/60 Hz |
[Ue] Rated Operational Voltage | power circuit: <= 300 V DC 25...400 Hz power circuit: <= 690 V AC |
Brand | Schneider Electric |