LC1D09M7

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil

1/1
LC1D09M7

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil

In stock
SKU
LC1D09M7
Rp ‎354.845
Add to compare
CHECK DELIVERY TIME & COD AVAILABILITY


No sellers found for this product.

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil

Rp ‎354.845

Description

TeSys D contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). It provides a 220V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability to demanding applications. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Product details

  • auxiliary contacts type
    type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
    type mirror contact 1 NC conforming to IEC 60947-4-1
  • Operating Altitude
    0...3000 m
  • Width
    45 mm
  • Pole Contact Composition
    3 NO
  • [Ie] Rated Operational Current
    9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
  • Operating Time
    12...22 ms closing
    4...19 ms opening
  • Mounting support
    plate
    rail
  • Ambient Air Temperature For Operation
    -40-60 °C
    60-70 °C with derating
  • [Uc] Control Circuit Voltage
    220 V AC 50/60 Hz
  • [Ith] Conventional Free Air Thermal Current
    25 A (at 60 °C) for power circuit
    10 A (at 60 °C) for signalling circuit
  • Product Or Component Type
    contactor
  • standards
    CSA C22.2 No 14
    EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 508
    IEC 60335-1
  • Product Certifications
    BV
    LROS (Lloyds register of shipping)
    UL
    GOST
    GL
    DNV
    CSA
    RINA
    CCC
    UKCA
  • Range of product
    TeSys D
    TeSys Deca
  • Overvoltage Category
    III
  • Net Weight
    0.32 kg
  • Depth
    86 mm
  • Weight (in Kg)
    0.351
  • Ambient Air Temperature for Storage
    -60-80 °C
  • Compatibility Code
    LC1D
  • Device Short Name
    LC1D
  • Height
    77 mm
  • Mechanical Durability
    15 Mcycles
  • Protective Treatment
    TH conforming to IEC 60068-2-30
  • Insulation Resistance
    > 10 MOhm for signalling circuit
  • Minimum Switching Current
    5 mA for signalling circuit
  • Minimum Switching Voltage
    17 V for signalling circuit
  • Pollution Degree
    3
  • Poles Description
    3P
  • Utilisation Category
    AC-4
    AC-3
    AC-1
    AC-3e
  • Average Impedance
    2.5 mOhm - Ith 25 A 50 Hz for power circuit
  • Auxiliary Contact Composition
    1 NO + 1 NC
  • Contact Compatibility
    M2
  • Contactor Application
    motor control
    resistive load
  • Motor Starter Type
    direct on-line contactor
  • Protective Cover
    with
  • Signalling Circuit Frequency
    25...400 Hz
  • Mechanical Robustness
    vibrations contactor open: 2 Gn, 5...300 Hz
    vibrations contactor closed: 4 Gn, 5...300 Hz
    shocks contactor open: 10 Gn for 11 ms
    shocks contactor closed: 15 Gn for 11 ms
  • [IP] Degree of Protection
    IP20 front face conforming to IEC 60529
  • Connections Terminals
    power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
    power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
    power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
    power circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
    power circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
    power circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
    control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
    control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
    control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
    control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
    control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
    control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
  • Flame Retardance
    V1 conforming to UL 94
  • Tightening Torque
    power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
  • [Ue] Rated Operational Voltage
    power circuit: <= 690 V AC 25...400 Hz
    power circuit: <= 300 V DC
  • [Ui] Rated Insulation Voltage
    power circuit: 690 V conforming to IEC 60947-4-1
    power circuit: 600 V CSA certified
    power circuit: 600 V UL certified
    signalling circuit: 690 V conforming to IEC 60947-1
    signalling circuit: 600 V CSA certified
    signalling circuit: 600 V UL certified
  • [Uimp] Rated Impulse Wthstand Voltage
    6 kV conforming to IEC 60947
  • Associated Fuse Rating
    10 A gG for signalling circuit conforming to IEC 60947-5-1
    25 A gG at <= 690 V coordination type 1 for power circuit
    20 A gG at <= 690 V coordination type 2 for power circuit
  • Climatic Withstand
    conforming to IACS E10
    conforming to IEC 60947-1 Annex Q category D
  • Coil Technology
    without built-in suppressor module
  • Contactor Coil Voltage
    220 V AC standard
  • Control Circuit Type
    AC at 50/60 Hz
  • Control Circuit Voltage Limits
    0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
    0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
    0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
    1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
  • Electrical Durability
    0.6 Mcycles 25 A AC-1 at Ue <= 440 V
    2 Mcycles 9 A AC-3 at Ue <= 440 V
    2 Mcycles 9 A AC-3e at Ue <= 440 V
  • Fire Resistance
    850 °C conforming to IEC 60695-2-1
  • Heat Dissipation
    2-3 W at 50/60 Hz
  • Hold-In Power Consumption In VA
    7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
  • Inrush Power In VA
    70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
    70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
  • Irms Rated Making Capacity
    250 A at 440 V for power circuit conforming to IEC 60947
    140 A AC for signalling circuit conforming to IEC 60947-5-1
    250 A DC for signalling circuit conforming to IEC 60947-5-1
  • Maximum Operating Rate
    3600 cyc/h 60 °C
  • Motor Power HP
    1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
    2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
    5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
    7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
    0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
  • Motor Power KW
    2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
    4 kW at 380...400 V AC 50/60 Hz (AC-3)
    4 kW at 415...440 V AC 50/60 Hz (AC-3)
    5.5 kW at 500 V AC 50/60 Hz (AC-3)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
    2.2 kW at 400 V AC 50/60 Hz (AC-4)
    2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
    4 kW at 380...400 V AC 50/60 Hz (AC-3e)
    4 kW at 415...440 V AC 50/60 Hz (AC-3e)
    5.5 kW at 500 V AC 50/60 Hz (AC-3e)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
  • Power Dissipation Per Pole
    1.56 W AC-1
    0.2 W AC-3
    0.2 W AC-3e
  • power_range
    1.1-2 kW at 200-240 V 3 phases
    2.2-3 kW at 380-440 V 3 phases
    4-6 kW at 380-440 V 3 phases
    4-6 kW at 480-500 V 3 phases
  • Rated Breaking Capacity
    250 A at 440 V for power circuit conforming to IEC 60947
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
  • [Icw] rated short-time withstand current
    105 A 40 °C - 10 s for power circuit
    210 A 40 °C - 1 s for power circuit
    30 A 40 °C - 10 min for power circuit
    61 A 40 °C - 1 min for power circuit
    100 A - 1 s for signalling circuit
    120 A - 500 ms for signalling circuit
    140 A - 100 ms for signalling circuit
more specification
less specification

Reviews

Write Your Own Review
You're reviewing:TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil
Your Rating

* Required Field