TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 220 V AC coil
Product Documents
Description
TeSys D contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). It provides a 220V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability to demanding applications. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Product details
-
auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1 -
Operating Altitude0...3000 m
-
Width45 mm
-
Pole Contact Composition3 NO
-
[Ie] Rated Operational Current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit -
Operating Time12...22 ms closing
4...19 ms opening -
Mounting supportplate
rail -
Ambient Air Temperature For Operation-40-60 °C
60-70 °C with derating -
[Uc] Control Circuit Voltage220 V AC 50/60 Hz
-
[Ith] Conventional Free Air Thermal Current25 A (at 60 °C) for power circuit
10 A (at 60 °C) for signalling circuit -
Product Or Component Typecontactor
-
standardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1 -
Product CertificationsBV
LROS (Lloyds register of shipping)
UL
GOST
GL
DNV
CSA
RINA
CCC
UKCA -
Range of productTeSys D
TeSys Deca -
Overvoltage CategoryIII
-
Net Weight0.32 kg
-
Depth86 mm
-
Weight (in Kg)0.351
-
Ambient Air Temperature for Storage-60-80 °C
-
Compatibility CodeLC1D
-
Device Short NameLC1D
-
Height77 mm
-
Mechanical Durability15 Mcycles
-
Protective TreatmentTH conforming to IEC 60068-2-30
-
Insulation Resistance> 10 MOhm for signalling circuit
-
Minimum Switching Current5 mA for signalling circuit
-
Minimum Switching Voltage17 V for signalling circuit
-
Pollution Degree3
-
Poles Description3P
-
Utilisation CategoryAC-4
AC-3
AC-1
AC-3e -
Average Impedance2.5 mOhm - Ith 25 A 50 Hz for power circuit
-
Auxiliary Contact Composition1 NO + 1 NC
-
Contact CompatibilityM2
-
Contactor Applicationmotor control
resistive load -
Motor Starter Typedirect on-line contactor
-
Protective Coverwith
-
Signalling Circuit Frequency25...400 Hz
-
Mechanical Robustnessvibrations contactor open: 2 Gn, 5...300 Hz
vibrations contactor closed: 4 Gn, 5...300 Hz
shocks contactor open: 10 Gn for 11 ms
shocks contactor closed: 15 Gn for 11 ms -
[IP] Degree of ProtectionIP20 front face conforming to IEC 60529
-
Connections Terminalspower circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
power circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
power circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
power circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
power circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
power circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end -
Flame RetardanceV1 conforming to UL 94
-
Tightening Torquepower circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 -
[Ue] Rated Operational Voltagepower circuit: <= 690 V AC 25...400 Hz
power circuit: <= 300 V DC -
[Ui] Rated Insulation Voltagepower circuit: 690 V conforming to IEC 60947-4-1
power circuit: 600 V CSA certified
power circuit: 600 V UL certified
signalling circuit: 690 V conforming to IEC 60947-1
signalling circuit: 600 V CSA certified
signalling circuit: 600 V UL certified -
[Uimp] Rated Impulse Wthstand Voltage6 kV conforming to IEC 60947
-
Associated Fuse Rating10 A gG for signalling circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit -
Climatic Withstandconforming to IACS E10
conforming to IEC 60947-1 Annex Q category D -
Coil Technologywithout built-in suppressor module
-
Contactor Coil Voltage220 V AC standard
-
Control Circuit TypeAC at 50/60 Hz
-
Control Circuit Voltage Limits0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz
1...1.1 Uc (60-70 °C):operational AC 50/60 Hz -
Electrical Durability0.6 Mcycles 25 A AC-1 at Ue <= 440 V
2 Mcycles 9 A AC-3 at Ue <= 440 V
2 Mcycles 9 A AC-3e at Ue <= 440 V -
Fire Resistance850 °C conforming to IEC 60695-2-1
-
Heat Dissipation2-3 W at 50/60 Hz
-
Hold-In Power Consumption In VA7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7-7 VA 50 Hz cos phi 0.3 (at 20 °C) -
Inrush Power In VA70-70 VA 60 Hz cos phi 0.75 (at 20 °C)
70-70 VA 50 Hz cos phi 0.75 (at 20 °C) -
Irms Rated Making Capacity250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1 -
Maximum Operating Rate3600 cyc/h 60 °C
-
Motor Power HP1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
0.33 hp at 115 V AC 50/60 Hz for 1 phase motors -
Motor Power KW2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
4 kW at 380...400 V AC 50/60 Hz (AC-3)
4 kW at 415...440 V AC 50/60 Hz (AC-3)
5.5 kW at 500 V AC 50/60 Hz (AC-3)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
2.2 kW at 400 V AC 50/60 Hz (AC-4)
2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
4 kW at 380...400 V AC 50/60 Hz (AC-3e)
4 kW at 415...440 V AC 50/60 Hz (AC-3e)
5.5 kW at 500 V AC 50/60 Hz (AC-3e)
5.5 kW at 660...690 V AC 50/60 Hz (AC-3e) -
Power Dissipation Per Pole1.56 W AC-1
0.2 W AC-3
0.2 W AC-3e -
power_range1.1-2 kW at 200-240 V 3 phases
2.2-3 kW at 380-440 V 3 phases
4-6 kW at 380-440 V 3 phases
4-6 kW at 480-500 V 3 phases -
Rated Breaking Capacity250 A at 440 V for power circuit conforming to IEC 60947
-
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 -
[Icw] rated short-time withstand current105 A 40 °C - 10 s for power circuit
210 A 40 °C - 1 s for power circuit
30 A 40 °C - 10 min for power circuit
61 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit