Schneider Electric TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A - 220 V AC 50/60 Hz coil

LC1D80M7
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Description

TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 80A/1000V AC-3/AC-3e (37kW@400V). It provides a 220V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach).

Product Details

Weight (in Kg) 1.56
Net weight 1.59 kg
auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Pole Contact Composition 3 NO
Product Or Component Type contactor
Mechanical Durability 4 Mcycles
Protective Treatment TH conforming to IEC 60068-2-30
Insulation Resistance > 10 MOhm for signalling circuit
Minimum Switching Current 5 mA for signalling circuit
Minimum Switching Voltage 17 V for signalling circuit
Poles Description 3P
Average Impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Auxiliary Contact Composition 1 NO + 1 NC
Contact Compatibility M11
Contactor Application motor control
resistive load
Motor Starter Type direct on-line contactor
Protective Cover with
Signalling Circuit Frequency 25...400 Hz
[IP] Degree of Protection IP20 front face conforming to IEC 60529
Connections Terminals control circuit: screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
control circuit: screw clamp terminals 1 cable(s) 1-2.5 mm²flexible with cable end
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
control circuit: screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
control circuit: screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
control circuit: screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
power circuit: connector 1 cable(s) 4-50 mm²flexible without cable end
power circuit: connector 2 cable(s) 4-25 mm²flexible without cable end
power circuit: connector 1 cable(s) 4-50 mm²flexible with cable end
power circuit: connector 2 cable(s) 4-16 mm²flexible with cable end
power circuit: connector 1 cable(s) 4-50 mm²solid without cable end
power circuit: connector 2 cable(s) 4-25 mm²solid without cable end
[Uimp] Rated Impulse Wthstand Voltage 8 kV conforming to IEC 60947
Irms Rated Making Capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1100 A at 440 V for power circuit conforming to IEC 60947
power_range 55-100 kW at 480-500 V 3 phases
15-25 kW at 200-240 V 3 phases
30-50 kW at 380-440 V 3 phases
30-50 kW at 480-500 V 3 phases
Ambient air temperature for operation -40-60 °C
60-70 °C with derating
Range of Product TeSys D
Tightening Torque control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
power circuit: 12 N.m - on connector hexagonal screw head 4 mm
control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product Certifications GOST
RINA
CCC
CSA
BV
DNV
GL
LROS (Lloyds register of shipping)
UL
Mechanical Robustness vibrations contactor open: 2 Gn, 5...300 Hz
shocks contactor open: 8 Gn for 11 ms
vibrations contactor closed: 3 Gn, 5...300 Hz
shocks contactor closed: 10 Gn for 11 ms
[Ith] Conventional Free Air Thermal Current 10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit
[ui] Rated Insulation Voltage power circuit: 600 V CSA certified
power circuit: 600 V UL certified
power circuit: 1000 V conforming to IEC 60947-4-1
signalling circuit: 690 V conforming to IEC 60947-1
signalling circuit: 600 V CSA certified
signalling circuit: 600 V UL certified
Associated Fuse Rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit
Mounting support plate
rail
Control Circuit Type AC at 50/60 Hz
Control Circuit Voltage Limits 0.85...1.1 Uc (-40-55 °C):operational AC 60 Hz
0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40-55 °C):operational AC 50 Hz
1...1.1 Uc (55-70 °C):operational AC 50/60 Hz
Electrical Durability 0.8 Mcycles 125 A AC-1 at Ue <= 440 V
1.5 Mcycles 80 A AC-3 at Ue <= 440 V
1.5 Mcycles 80 A AC-3e at Ue <= 440 V
Fire Resistance 850 °C conforming to IEC 60695-2-1
Heat Dissipation 6-10 W at 50/60 Hz
Hold-In Power Consumption In VA 26-26 VA 60 Hz cos phi 0.3 (at 20 °C)
26-26 VA 50 Hz cos phi 0.3 (at 20 °C)
Inrush Power In VA 245-245 VA 60 Hz cos phi 0.75 (at 20 °C)
245-245 VA 50 Hz cos phi 0.75 (at 20 °C)
Maximum Operating Rate 3600 cyc/h 60 °C
Motor Power Kw 22 kW at 220...230 V AC 50/60 Hz (AC-3)
37 kW at 380...400 V AC 50/60 Hz (AC-3)
45 kW at 415...440 V AC 50/60 Hz (AC-3)
55 kW at 500 V AC 50/60 Hz (AC-3)
45 kW at 660...690 V AC 50/60 Hz (AC-3)
45 kW at 1000 V AC 50/60 Hz (AC-3)
15 kW at 400 V AC 50/60 Hz (AC-4)
Operating Time 20...35 ms closing
6...20 ms opening
Power Dissipation Per Pole 5.1 W AC-3
12.5 W AC-1
5.1 W AC-3e
Rated Breaking Capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 40 °C - 10 s for power circuit
990 A 40 °C - 1 s for power circuit
135 A 40 °C - 10 min for power circuit
320 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Flame Retardance V1 conforming to UL 94
Contactor Coil Voltage 220 V AC standard
Safety Reliability Level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Climatic Withstand conforming to IACS E10
Coil Technology without built-in suppressor module
Motor Power Hp 7.5 hp at 120 V AC 50/60 Hz for 1 phase motors
15 hp at 230/240 V AC 50/60 Hz for 1 phase motors
30 hp at 200/208 V AC 50/60 Hz for 3 phases motors
30 hp at 230/240 V AC 50/60 Hz for 3 phases motors
60 hp at 460/480 V AC 50/60 Hz for 3 phases motors
60 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Device short name LC1D
Depth 130 mm
Ambient air temperature for storage -60-80 °C
Height 127 mm
Overvoltage Category III
width 85 mm
Pollution degree 3
Utilisation category AC-1
AC-4
AC-3
AC-3e
Operating altitude 0...3000 m
Non-Overlap Time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Compatibility code LC1D
[Uc] Control Circuit Voltage 220 V AC 50/60 Hz
[Ue] Rated Operational Voltage power circuit: <= 300 V DC 25...400 Hz
power circuit: <= 690 V AC
Brand Schneider Electric

Seller Information

Documents

Extended Warranty

Reviews

Write Your Own Review
You're reviewing: Schneider Electric TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 80 A - 220 V AC 50/60 Hz coil
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.