Net weight |
1.61 kg |
Product or Component Type |
contactor |
[Uc] Control Circuit Voltage |
48 V AC 50/60 Hz |
auxiliary contacts type |
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1, type mirror contact 1 NC conforming to IEC 60947-4-1 |
Pole Contact Composition |
3 NO |
Mechanical Durability |
4 Mcycles |
Protective Treatment |
TH conforming to IEC 60068-2-30 |
Insulation Resistance |
> 10 MOhm for signalling circuit |
Minimum Switching Current |
5 mA for signalling circuit |
Minimum Switching Voltage |
17 V for signalling circuit |
Poles Description |
3P |
Average Impedance |
0.8 mOhm - Ith 125 A 50 Hz for power circuit |
Auxiliary Contact Composition |
1 NO + 1 NC |
Contact Compatibility |
M11 |
Contactor Application |
motor control,resistive load |
Protective Cover |
with |
Signalling Circuit Frequency |
25...400 Hz |
Range of Product |
TeSys Deca |
Standards |
EN/IEC 60947-1,EN/IEC 60947-4-1,EN/IEC 60947-5-1,UL 60947-4-1,UL 60947-5-1,CSA C22.2 No 60947-4-1,CSA C22.2 No 60947-5-1,GB/T 14048.4 |
Mechanical Robustness |
vibrations contactor open (2 Gn, 5...300 Hz),shocks contactor open (8 Gn for 11 ms),vibrations contactor closed (3 Gn, 5...300 Hz),shocks contactor closed (10 Gn for 11 ms) |
Associated Fuse Rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1,200 A gG at <= 690 V coordination type 1 for power circuit,160 A gG at <= 690 V coordination type 2 for power circuit |
Mounting support |
rail,plate |
Control Circuit Type |
AC at 50/60 Hz standard |
Electrical Durability |
1.2 Mcycles 95 A AC-3,1.3 Mcycles 125 A AC-1,1.2 Mcycles 95 A AC-3e |
Heat Dissipation |
6-10 W at 50/60 Hz |
Operating Time |
20...35 ms closing,6...20 ms opening |
Power Dissipation Per Pole |
12.5 W AC-1,7.2 W AC-3,7.2 W AC-3e |
Rated Breaking Capacity |
1100 A at 440 V for power circuit conforming to IEC 60947 |
Flame Retardance |
V1 conforming to UL 94 |
Safety Reliability Level |
B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1,B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Coil Technology |
without built-in suppressor module |
Motor Power Hp |
7.5 hp at 120 V AC 60 Hz for 1 phase motors,15 hp at 230/240 V AC 60 Hz for 1 phase motors,30 hp at 200/208 V AC 60 Hz for 3 phases motors,30 hp at 230/240 V AC 60 Hz for 3 phases motors,60 hp at 460/480 V AC 60 Hz for 3 phases motors,60 hp at 575/600 V AC 60 Hz for 3 phases motors |
Device short name |
LC1D |
Depth |
130 mm |
Height |
127 mm |
Overvoltage Category |
III |
width |
85 mm |
Pollution degree |
3 |
Utilisation category |
AC-3,AC-3e,AC-4,AC-1 |
Operating altitude |
0...3000 m |
Non-Overlap Time |
1.5 ms on de-energisation between NC and NO contact,1.5 ms on energisation between NC and NO contact |
Compatibility code |
LC1D |
Range |
TeSys |
IP degree of protection |
IP20 front face conforming to IEC 60529 |