TPRST025

Schneider Electric Direct online starter, TeSys island, 30A AC-1, 25A AC-3, 11kW / 15hp

1/1
TPRST025

Schneider Electric Direct online starter, TeSys island, 30A AC-1, 25A AC-3, 11kW / 15hp

In stock
SKU
TPRST025
Rp ‎ 4.048.200
To View the best prices please sign in or register.
CHECK DELIVERY TIME & COD AVAILABILITY

Add to compare

No sellers found for this product.

Schneider Electric Direct online starter, TeSys island, 30A AC-1, 25A AC-3, 11kW / 15hp

Rp ‎ 4.048.200

Description

TeSys island direct starter, 3 poles, 25A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 25A and motors up to 11kW@400V / 15hp@480V. It provides motor protection functions including thermal overload (setting 0.5-25A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Product details

  • Activity
    PPCTR
  • Weight (in Kg)
    0.774
  • Net weight
    0.718 kg
  • Product Or Component Type
    motor starter
  • Mounting Mode
    horizontal and vertical (35 mm symmetrical DIN rail)
  • Mechanical Durability
    30 Mcycles
  • Protective Treatment
    TC
  • Reset
    remotely or automatically
  • Poles Description
    3P (3 NO)
  • Average Impedance
    2 mOhm - Ith 30 A 50 Hz
  • Motor Starter Type
    direct on line
  • Thermal Protection Adjustment Range
    0.5-25 A
  • [IP] Degree of Protection
    IP20
  • Connections Terminals
    screw-clamp terminals 1 cable(s) 1.5-10 mm² (AWG 16...AWG 8) rigid
    screw-clamp terminals 2 cable(s) 1.5-10 mm² (AWG 16...AWG 8) rigid
    screw-clamp terminals 1 cable(s) 2.5-10 mm² (AWG 14...AWG 8) flexible without cable end
    screw-clamp terminals 2 cable(s) 2.5-10 mm² (AWG 14...AWG 8) flexible without cable end
    screw-clamp terminals 1 cable(s) 1.5-10 mm² (AWG 16...AWG 10) flexible with cable end
    screw-clamp terminals 2 cable(s) 1.5-6 mm² (AWG 16...AWG 10) flexible with cable end
  • [Uimp] Rated Impulse Wthstand Voltage
    6 kV conforming to IEC 60947-1
  • Irms Rated Making Capacity
    450 A at 440 V conforming to IEC 60947
  • protection_type
    thermal overload protection
    motor overheat
    overcurrent
    undercurrent
    jam
    long start
    stall
    rapid cycle lockout
    rapid restart lockout
    phase sequence
    phase reversal
    phase loss
    phase unbalance
    ground current
  • Ambient air temperature for operation
    -10-50 °C without derating
    50-60 °C with current derating
  • Tightening Torque
    2.5-2.5 N.m - with screwdriver flat Ø 6 mm
    2.5-2.5 N.m - with screwdriver Philips No 3
  • Standards
    EN/IEC 60947-1
    EN/IEC 60947-4-1
    UL 60947-4-1
    CSA C22.2 No 60947-4-1
  • Product Certifications
    CCC
    UL
    CSA
    EAC
  • [Ith] Conventional Free Air Thermal Current
    30 A (at 50 °C)
  • [ui] Rated Insulation Voltage
    690 V conforming to IEC 60947-4-1
    600 V conforming to UL 60947-4-1
    600 V conforming to CSA C22.2 No 60947-4-1
  • Electrical Durability
    1.65 Mcycles 25 A AC-3 at Ue 440 V
    2 Mcycles 30 A AC-1 at Ue 440 V
  • Fire Resistance
    960 °C conforming to UL 94
    850 °C conforming to IEC 60695-2-1
    650 °C conforming to IEC 60695-2-12
  • Maximum Operating Rate
    3600 cyc/mn AC-3
  • Motor Power Kw
    5.5 kW at 230 V 50 Hz (AC-3)
    11 kW at 380...415 V 50 Hz (AC-3)
    11 kW at 440 V 50 Hz (AC-3)
    15 kW at 500 V 50 Hz (AC-3)
    15 kW at 690 V 50 Hz (AC-3)
  • Operating Time
    < 100 ms closing
    < 30 ms opening
  • Power Dissipation Per Pole
    1.25 W AC-3 - Ith 25 A
    1.8 W AC-1 - Ith 30 A
  • Rated Breaking Capacity
    450 A at 440 V conforming to IEC 60947
  • [Icw] rated short-time withstand current
    380 A 40 °C - 1 s
    240 A 40 °C - 10 s
    120 A 40 °C - 1 min
    50 A 40 °C - 10 min
  • Safety Reliability Level
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
  • Motor Power Hp
    2 hp at 120 V AC 60 Hz for 1 phase motors
    3 hp at 240 V AC 60 Hz for 1 phase motors
    7.5 hp at 208 V AC 60 Hz for 3 phases motors
    7.5 hp at 240 V AC 60 Hz for 3 phases motors
    15 hp at 480 V AC 60 Hz for 3 phases motors
    20 hp at 600 V AC 60 Hz for 3 phases motors
  • Product Compatibility
    TPRBC bus coupler
    TPRVM voltage interface module
  • Local Signalling
    1 LED (green/red) for DS (device status)
    1 LED (green/red) for LS (load status)
  • Electromagnetic Compatibility
    electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
    radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3
    fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4
    surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
    surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5
    conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
  • Thermal Overload Class
    class 5…30
  • Current Consumption
    160 mA contactor sealed
    160 mA contactor closing
  • Shock Resistance
    15 gn (duration = 11 ms) conforming to IEC 60068-2-27
  • Function Available
    upstream voltage presence detection
    electrical line and load protection
    power and energy monitoring when connected with TPRVM voltage module
  • Metering Type
    time device ON
    time device switch ON
    number of faults
    number of switching cycles
    number of device power cycles
    average current Iavg
    average voltage Vavg
    max current Imax
    max voltage Vmax
    active and reactive power with voltage module
    active and reactive energy with voltage module
    true power factor with voltage module
  • Device Presentation
    direct starter connected to an automation controller through a bus coupler
    operational only when connected to a bus coupler
  • Device short name
    TPRST
  • Depth
    115 mm
  • Ambient air temperature for storage
    -25-70 °C
  • Height
    121 mm
  • Overvoltage Category
    III for Ue <= 480 V
    II for Ue <= 690 V
  • width
    45 mm
  • Pollution degree
    2
  • Utilisation category
    AC-1
    AC-2
    AC-3
    AC-4
  • Operating altitude
    0...2000 m without derating
  • Vibration Resistance
    1.5 mm peak to peak (f= 3-13 Hz) conforming to IEC 60068-2-6
    1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6
  • Relative humidity
    5-95 %
  • Power Dissipation in w
    6.6 W at Ie AC-3
  • [Uc] Control Circuit Voltage
    24 V DC supplied by the bus coupler
  • [Ue] Rated Operational Voltage
    <= 480 V AC 47...63 Hz for overvoltage cat. III
    <= 690 V AC 47...63 Hz for overvoltage cat. II
  • Brand
    Schneider Electric
more specification
less specification

Seller Information

Reviews

Write Your Own Review
You're reviewing:Schneider Electric Direct online starter, TeSys island, 30A AC-1, 25A AC-3, 11kW / 15hp
Your Rating

* Required Field