residual current monitoring relay, Vigirex RH99M, 30mA to 30A, 380/415 VAC 50/60Hz, DIN rail mounting

56194
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Out of stock

Description

VigiPacT RH99M is a DIN rail mounting residual current monitoring relay. It monitor drops in electrical insulation due to ageing of cables or extensions in the installation. It measures the earth leakage current in an electrical installation via its associated toroid. A control signal is issued by the relay when the residual-current operating threshold is overrun. The operational supply voltage is 380/415VAC 50/60Hz. The current sensitivity is selectable with 9 thresholds from 30 mA to 30 A. The time delay is selectable with 9 settings from instantaneous to 4.5s. There is an automatic reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.

Product Details

Activity PPCCB
[uimp] Rated Impulse Withstand Voltage 8 kV
[us] Rated Supply Voltage 380...415 V AC 50/60 Hz 55...110 %
Ambient Air Temperature for Operation -35-70 °C
Ambient Air Temperature for Storage -55-85 °C
Compatibility Code RH99M
Depth 74 mm
Device Short Name RH99M
Electromagnetic Compatibility conducted and radiated emissions: , B, conforming to CISPR 11
Height 81 mm
Ik Degree of Protection IK07 conforming to EN 50102
Ip Degree of Protection IP40 on front face: conforming to EN/IEC 60529
Mechanical Robustness fire resistance conforming to IEC 60695-2-1
Minimum Load 10 mA at 12 V
Mounting Support DIN rail
Net Weight 0.3 kg
Overvoltage Category IV
Product or Component Type monitoring relay
Range VigiPacT
Range Compatibility TOA earth leakage current sensor
Tightening Torque auxiliary power supply: 0.6-0.6 N.m top
Width 54 mm
Wire Stripping Length auxiliary power supply: 7 mm for top connection
9 Mm Pitches 6
Connections - Terminals auxiliary power supply: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12
[ithe] Conventional Enclosed Thermal Current 8:00 AM
Earth Leakage Current 0.03-30 A
Earthing System TN-S
Electrical Shock Protection Class class II
Monitoring electronics (continuous)
Network Rated Voltage 1000-1000 V - AC at 50/60 Hz (maximum)
Power Consumption in Va 4 VA
Relay Application monitoring relay
Residual Earth-leakage Sensitity Adjustment Type adjustable 9 settings
Residual Earth-leakage Time Delay Adjustment Type instantaneous for 0.03-0.03 A
Tamperproof of Settings protected by sealable cover
Test Function remote test
Threshold Setting 0.03...30 A alarm
Type of Measurement earth fault current internal measurement, range: 80...100 %
Type of Setting selector
Pollution Degree 3 conforming to IEC 60664-1
Relative Humidity 95-95 % at 55-55 °C

Seller Information

Documents

Reviews

Write Your Own Review
You're reviewing: residual current monitoring relay, Vigirex RH99M, 30mA to 30A, 380/415 VAC 50/60Hz, DIN rail mounting
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.