Activity |
PPCTR |
Part Number |
LC1E1810B5 |
Weight |
346.9 g |
Package1 Length*Width*Height |
7.5 cm x 5.0 cm x 8.6 cm |
[Ie] rated operational current |
32 A (at <55 °C) at <= 415 V AC AC-1 for power circuit, 18 A (at <55 °C) at <= 440 V AC AC-3 for power circuit |
[Ith] conventional free air thermal current |
32 A (at 55 °C) |
[Uc] control circuit voltage |
24 V AC 50 Hz |
[ue] Rated Operational Voltage |
power circuit: <= 690 V AC 50/60 Hz |
[Ui] rated insulation voltage |
690 V conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage |
6 kV coil not connected to the power circuit conforming to IEC 60947 |
ambient air temperature for operation |
-5-55 °C |
ambient air temperature for storage |
-60-80 °C |
associated fuse rating |
10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1, 35 A gG at <= 690 V coordination type 1 for power circuit |
auxiliary contact composition |
1 NO |
average impedance |
2.5 mOhm - Ith 32 A 50 Hz for power circuit |
colour |
grey (RAL 7011) |
connections - terminals |
power circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end |
contactor application |
resistive load, motor control |
control circuit type |
AC at 50 Hz |
control circuit voltage limits |
operational: 0.85...1.1 Uc at 50 Hz (at <55 °C), drop-out: 0.3...0.6 Uc at 50 Hz (at <55 °C) |
depth |
80 mm |
device short name |
LC1E |
electrical durability |
300000 cycles AC-1, 1200000 cycles AC-3 |
fire resistance |
850 °C conforming to IEC 60695-2-1 |
heat dissipation |
2-3 W for control circuit |
height |
74 mm |
hold-in power consumption in VA |
8.3-8.3 VA 50 Hz cos phi 0.3 (at 20 °C), 8.5-8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
inrush power in VA |
95-95 VA 50 Hz cos phi 0.75 (at 20 °C), 95-95 VA 60 Hz cos phi 0.75 (at 20 °C) |
insulation resistance |
> 10 MOhm for control circuit |
IP degree of protection |
IP2x conforming to IEC 60529 |
Irms rated making capacity |
180 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
maximum operating rate |
1800 cyc/h 60 °C |
mechanical durability |
10000000 cycles |
mechanical robustness |
vibrations contactor open: 1.5 Gn, 5...300 Hz, vibrations contactor closed: 3 Gn, 5...300 Hz, shocks contactor open: 7 Gn for 11 ms, shocks contactor closed: 10 Gn for 11 ms |
minimum switching current |
5 mA for control circuit |
minimum switching voltage |
17 V for control circuit |
motor power kW |
4 kW at 220...230 V AC 50/60 Hz, 7.5 kW at 380...400 V, 9 kW at 415 V, 9 kW at 440 V, 10 kW at 500 V, 10 kW at 660...690 V |
mounting support |
plate, DIN rail |
net weight |
0.3 kg |
non-overlap time |
1.5 ms on energisation guaranteed between NC and NO contact, 1.5 ms on de-energisation guaranteed between NC and NO contact |
operating altitude |
3000 m without derating |
operating time |
12...22 ms on closing, 4...19 ms on opening |
overvoltage category |
III |
permissible ambient air temperature around the device |
-20-70 °C at Uc |
pole contact composition |
3 NO |
Poles Description |
3P |
pollution degree |
3 |
power dissipation per pole |
0.81 W AC-3, 2.6 W AC-1 |
product certifications |
EAC, CE |
product or component type |
contactor |
protective treatment |
TH (pollution degree 3) conforming to IEC 60068-2-30 test Db |
range |
EasyPact |
rated breaking capacity |
144 A at 440 V for power circuit conforming to IEC 60947 |
standards |
IEC 60947-5-1, IEC 60947-4-1, IEC 60947-1 |
tightening torque |
power circuit: 1.2 N.m, control circuit: 1.2 N.m, power circuit: 1.4 N.m, control circuit: 1.4 N.m |
utilisation category |
AC-1, AC-3 |
width |
45 mm |
[Icw] rated short-time withstand current |
145 A 40 °C - 10 s for power circuit, 84 A 40 °C - 60 s for power circuit, 40 A 40 °C - 600 s for power circuit |