control relay, TeSys K, 4P(3NO+1NC), 690V, 230V AC standard coil

CA2KN31P7
Be the first one to review this.
login_green To View the best prices please Sign in / Register.
Only 0 left in stock.
plain-icon

Product Details

Activity PPCTR
Pincode Group default
Part Number CA2KN31P7
[Ith] conventional free air thermal current 10 A (at 50 °C)
[Uc] control circuit voltage 230 V AC 50/60 Hz
[Ui] rated insulation voltage 690 V conforming to IEC 60947, 750 V conforming to VDE 0110 group C, 690 V conforming to BS 5424, 600 V conforming to CSA C22.2 No 14
ambient air temperature for storage -50-80 °C
associated fuse rating 10 A gG conforming to IEC 60947, 10 A gG conforming to VDE 0660
compatibility code CA2K
connections - terminals screw clamp terminals 1 cable(s) 1.5-4 mm²solid, screw clamp terminals 2 cable(s) 1.5-4 mm²solid, screw clamp terminals 1 cable(s) 0.75-4 mm²flexible with cable end, screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end, screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end, screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible without cable end
contactor application control circuit
control circuit type AC at 50/60 Hz
control circuit voltage limits drop-out: 0.2...0.75 Uc (at <50 °C), operational: 0.8...1.15 Uc (at <50 °C)
depth 57 mm
device short name CA2K
flame retardance V1 conforming to UL 94, requirement 2 conforming to NF F 16-101, requirement 2 conforming to NF F 16-102
heat dissipation 1.3-1.3 W
height 58 mm
hold-in power consumption in VA 4.5-4.5 VA (at 20 °C)
inrush power in VA 30-30 VA (at 20 °C)
IP degree of protection IP2X
Irms rated making capacity 110 A conforming to IEC 60947
maximum operating rate 10000 cyc/h
mechanical durability 10 Mcycles
minimum switching current 5 mA
minimum switching voltage 17 V
mounting support rail, plate
net weight 0.18 kg
operating altitude 2000 m without derating
operating time 10...20 ms coil de-energisation and NO opening, 10...20 ms coil energisation and NO closing, 15...25 ms coil de-energisation and NC closing, 5...15 ms coil energisation and NC opening
pole contact composition 3 NO + 1 NC
product certifications CB Scheme, CCC, UL, CSA, EAC, CE, UKCA
product or component type control relay
protective treatment TC conforming to IEC 60068
range TeSys
range of product TeSys K control relay
rated operational voltage limits <= 690 V <= 400 Hz
tightening torque 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm, 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm, 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
utilisation category AC-15, DC-13
width 45 mm
Immunity to microbreaks 2 ms
Non overlap distance 0.5 mm
ambient air temperature for operation -25-50 °C
standards EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1
insulation resistance > 10 MOhm
mechanical robustness vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6, vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6, shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27, shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27

Seller Information

Documents

Reviews

Write Your Own Review
You're reviewing: control relay, TeSys K, 4P(3NO+1NC), 690V, 230V AC standard coil
* Required Field
loader
Loading...

check-circle You submitted your review for moderation.

Frequently Bought Together

Auxiliary contact block, TeSys K, 2NO + 2NC, screw terminals
LA1KN22

In stock

AED 40.00
AED 59.93
Auxiliary contact block, TeSys K, 3NO + 1NC, front mounting, screw clamp terminals
LA1KN31

In stock

AED 40.00
AED 60.00
Auxiliary contact block, TeSys K, 4NO, front mounting, screw clamp terminals
LA1KN40

In stock

AED 40.00
AED 60.00
Auxiliary contact block, TeSys K, 1NO + 3NC, front mounting, screw clamp terminals
LA1KN13

In stock

AED 40.00
AED 59.86
Auxiliary contact block, TeSys K, 4NC, front mounting, screw clamp terminals
LA1KN04

In stock

AED 40.00
AED 60.00