[ics] Rated Service Breaking Capacity |
35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2, 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2, 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage |
8 kV conforming to IEC 60947-2 |
breaking capacity |
85 kA at 240 V AC 50/60 Hz conforming to UL 508, 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2, 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2, 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2, 35 kA at 480 V AC 50/60 Hz conforming to UL 508, 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 15 kA at 600 V AC 50/60 Hz conforming to UL 508 |
Breaking Capacity Code |
F 36 kA 415 V AC |
Connection Pitch |
35 mm |
Downside Connection |
front |
Neutral Position |
left |
suitability for isolation |
yes conforming to EN/IEC 60947-2 |
Upside Connection |
front |
utilisation category |
category A |
ambient air temperature for storage |
-50-85 °C |
compatibility code |
NSX250 |
control type |
toggle |
depth |
86 mm |
device application |
distribution |
device short name |
NSX250F |
Electrical Durability |
10000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2, 10000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2, 20000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2, 5000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 |
height |
161 mm |
IK degree of protection |
IK07 conforming to IEC 62262 |
IP degree of protection |
IP40 conforming to IEC 60529 |
mechanical durability |
20000 cycles conforming to IEC 60947-2 |
mounting mode |
fixed |
mounting support |
backplate |
network frequency |
50/60 Hz |
network type |
AC |
Poles Description |
4P |
pollution degree |
3 conforming to IEC 60664-1 |
product certifications |
UL, CSA |
product or component type |
basic frame |
Protection Type |
without protection |
range |
ComPacT new generation |
range of product |
ComPacT NSX100...250 new generation |
width |
140 mm |
ambient air temperature for operation |
-25-70 °C |
standards |
EN/IEC 60947-2, UL 508 |
[Ui] rated insulation voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2 |